Model: GRAA15P
S/N: A2301904658001001 & A2301904658002001
Unit No.: GRCA15PPFBF0N6BX302A0CEFKLNPQRTVY56204
For Industrial/Commercial Use
Date of Mfgr: 1/19/2023, UNUSED
Standard Conditions (0-2000 Ft.):
Std. Orifice Size: 42, Alt: Under 2000',
Gas Type: Natural,
Max. Inlet Pressure: 14.0 In. W.C., Input: 150,000 BTU/Hr.
Max. Inlet Pressure: 6.5 In. W.C., Output: 120,000 BTU/Hr.
Normal Manifold Pressure: 3.5 In. W.C., Min. Output: 60,000 BTU/Hr.
Airflow: 1200-1800 CFM @ 0-2 In. W.C., ESP
For Operation At A Temperature Rise from 60 to 90 Degrees F
-------------------------------------------------
Unit Requirements:
Electrical Ratings:
VAC: 460, Hertz: 60, Phase: 3
Min. Supply Circuit Ampacity: 5.3 Amps
Max. Supply Fuse Rating: 10 Amps
Motor Requirements:
Motor Size: 2 HP, Motor Full Load Rating: 2.9 Amps
Control Circuit Requirements:
24 VAC, Transformer Size: 100 VA, Overcurrent Protection Device: 4 Amps.
Unit may be mounted on Combustible or Non-Combustible Material
For Use with Ducts. Min. Ambient Temperature: -40 Degrees F.
Conforms to UL 1995 and ANSI Z83.8 -2016
Certified to CSA C22.2 No. 236 and CSA 2.6 -2016
GAS FIRED PACKAGED DUCT FURNACE FOR INDUSTRIAL/COMMERCIAL USE
FOR OUTDOOR USE
GRCA15PPFBF0N6BX302A0CEFKLNPQRTVY56204
G: Gas Heating Equipment: GAS
R: Unit Type: Rooftop Heating Unit
C: Furnace Type: High Temp Rise (60-90F) LH
A: Development Sequence: First Generation
15: Input Capacity Single Furnace: 150 MBh Input
P: Venting Type: Power Venting
F: Main Power Supply: 460V/60Hz/3Ph
B: Main Power Supply Gas Control Option (Intermittent Pilot Ignition): Two-Stage
F0: Design Sequence: F0
N: Fuel Type: Natural Gas
6: Heat Exchanger Material: 3409 Stainless Steel Package (First Furnace Only)
B: Rooftop Arrangements: Blower (Standard)
X: Rooftop Heating Unit Motor Selection: 2 HP w/VFD
3: Motor Speed: Single Speed High Efficiency ODP 1800 RPM
0: No Coiling Coil Selection
2: Air Inlet Configuration: Outside Air w/Air Hood, Horizontal Inlet
A: Air Control and Damper Arrangements: Outside Air 2 Pos. Motor/SR
0: Non-California Shipment
MISC. OPTIONS:
C: Moisture Eliminators
E: Air Flow Proving Switch
F: Freezestat
K: Manual Blower Switch
L: 409 Stainless Steel Furnace Drip Pan
N: Double Wall Construction
P: Low Leak Dampers
Q: Clogged Filter Switch
R: High/Low Gas Pressure Limit Switches
T: Status Indicator Lights (Elec Cabinet)
V: Manual Reset High Limit Switch
Y: Ambient Lockout
5: 2" Pleated Media Filters
6: Service Convenience Package
VFD Accessories:
2: Factory Installed VFD
4: CO2 Sensor, 100% Outside Air